GB Conventional Emissions
Boiler Burner

Turnkey Boiler Burner Solutions Brochure
(PDF, 3.3 MB)
Burner Description:
The Zeeco GB Conventional Emissions burner is used for Boiler Applications.
Burner Design Features:
- Stable flame over a wide range of conditions
- High turndown of 10:1 or greater for most cases
- Compact Design makes this burner a great choice for retrofit applications
- Reasonable cost and great value
- Combustion air dampers are controlled by gears for precise control
- Bearings are used for the combustion air damper shafts for smooth, precise operation
- Configurations available: plenum mounted or individual wind-box
- 304 Stainless Steel fuel gas risers
- 310 Stainless Steel (Type HK) gas primary gas tip
- Center swirler
Burner Design Information
| Burner Model: | GB Conventional Emissions Burner |
| Fuels: | Gas Only or Combination Oil & Gas |
| Description: | Round Flame |
| NOx Reduction Method: | Conventional Emissions |
| Predicted NOx Emissions Range: | 25 ppmv wth 30% EFGR |
| Predicted NOx Emissions Range: | 30 ppmv wth 20% EFGR |
| Predicted NOx Emissions Range: | 35 ppmv wth 15% EFGR |
| Predicted NOx Emissions Range: | 50 ppmv wth 10% EFGR |
| Predicted NOx Emissions Range: | 70 ppmv wth 0% EFGR |
| Combustion Air Induction: | Forced Draft |
| Mounting Options: | Side-fired |
| Forced Draft Heat Release Range: | 1 MM to 350 MM Btu/hr [0.293 to 102.55 MW] |
| Turndown: | 10:1 |
| Typical Excess Air Range: | 10% to 25% |