GB Conventional Down-fired Burner

GB Conventional Down-Fired Burner GraphicBurner Description:

The Zeeco GB Conventional, round flame gas only burner for down-fired applications.

Burner Design Features:

Burner Design Information

Burner Model: GB Conventional Burner
Fuels: Gas Only
Description: Round Flame Conventional Emissions Burner
NOx Reduction Method: None
Predicted NOx Emissions Range (Natural Draft): 90 ppmv to 200 ppmv
Predicted NOx Emissions Range (600°F/316°C Air Preheat): 150 ppmv to 400 ppmv
Combustion Air Induction: Natural, Forced, Induced & Balanced Draft
Mounting Options: Down-fired
Natural Draft Heat Release Range: 1 MM to 12 MM Btu/hr [0.293 to 3.516 MW]
Forced Draft Heat Release Range: 1 MM to 18 MM Btu/hr [0.293 to 5.274 MW]
Turndown: 10:1
Typical Excess Air Range: 10% to 25%