CLSF FREE-JET
Round Flame Combination

Next Generation Round Flame Combination BurnerThe picture (right) is Zeeco’s CLSF Free-Jet combination burner in operation at our combustion test facility. This design offers state-of-the-art NOx reduction for combination oil and gas firing. NOx reduction for gas firing is achieved by the Free-Jet method of mixing the fuel gas with the inert products of combustion before the combustion occurs, resulting in lower thermal NOx production. The reduced NOx emissions from oil firing is achieved by “Pseudo Staging” of oil by our CB oil gun design. The result is a burner that can achieve very low NOx emissions with superior turndown. For natural draft applications, the burner is offered with a regen tile for oil stabilization. In forced draft applications, the burner is offered with a regen tile, cone or swirler depending upon the combustion air pressure drop available and customer requirements.

Burner Description:

The Zeeco CLSF Free-Jet burner is a Next Generation emissions round flame combination burner.

Burner Design Features:

Burner Design Information

Burner Model: CLSF Free-Jet Burner
Fuels: Combination Oil & Gas
Description: Round Flame Next Generation Emissions
NOx Reduction Method: Internal Flue Gas Recirculation by Free-Jet Mixing
Predicted NOx Emissions Range (Natural Draft): 6 ppmv to 20 ppmv
Predicted NOx Emissions Range (600°F/316°C Air Preheat): 10 ppmv to 25 ppmv
Predicted NOx Emissions Range (Natural Draft) with No. 2 oil fired: 80 ppmv to 120 ppmv
Predicted NOx Emissions Range (600°F/316°C Air Preheat) with
No. 2 oil fired:
120 ppmv to 180 ppmv
Predicted NOx Emissions Range (Natural Draft) with No. 6 oil fired: 160 ppmv to 220 ppmv
Predicted NOx Emissions Range (600°F/316°C Air Preheat) with
No. 6 oil fired:
215 ppmv to 280 ppmv
Combustion Air Induction: Natural, Forced, Induced & Balanced Draft
Mounting Options: Up-fired and Side-fired
Natural Draft Heat Release Range: 1 MM to 20 MM Btu/hr [0.293 to 5.860 MW]
Forced Draft Heat Release Range: 1 MM to 50 MM Btu/hr [0.293 to 14.65 MW]
Turndown: 10:1 gas & 3:1 oil
Typical Excess Air Range: 10% to 25%