ZEECO RESOURCES | Presentations

Achieving Ultra-Low NOx Emissions Without EFGR In Burner Retrofit Applications

Written by Zeeco | Jun 11, 2012 9:28:00 PM

International Flame Research Foundation – June 11-13, 2012 – Chateau de Maffliers, France

Problem

  • Requirement of ultra-low NOx emissions
  • Existing heater with set cutout and tube circle
  • Short flame length requirement
  • EFGR and SCR are not practical
  • High firebox temperature

Case Study: Dow in Pittsburg, CA USA

  • < 9 PPMV NOx requirement
  • 6.55 MM Kcal/hr heat release
  • 6.6 m firebox height
  • 926 C firebox temperature
  • 2.9 m tube circle
  • 994,964 Kcal/m2 heat flux density
  • 0.6 kg steam/kg fuel steam injection

Field Results

  • Emissions measured by 3 rd party agency to be reported to Enviromental Protection Agency
  • 5.94 PPMV NOx dry average
  • 2.51 PPMV CO dry average

Download Presentation